This code is improperly informed: ophyd/ophyd/utils/epics_pvs.py Lines 74 to 75 in 030c668
While very unusual, EPICS allows more than one Thanks for uncovering this little gem. I had not come across it before. The last common instances of double-dot PVs were excised from the APS control systems many years ago, before ophyd was conceived. I'm searching for the naming rules in the EPICS documentation. Time to call in an expert. |
@anjohnson : Can you provide a reference here to the rules about naming of EPICS process variables? If it makes a difference this issue is discussing Channel Access PV names. |
CA and PVA servers have their own different limitations and rules for PV names (also called channel names, the terms mean the same thing); the rules for an IOC server are different than for a PCAS or PVA servers. Thus the names you can use depend on the server that publishes the PV, and a generic client application should generally accept and send any string that the user enters (unless it only supports talking to an EPICS motor record say). A motor record is an object that lives in an IOC, so the characters up to the first When pointing to a specific field of an IOC record the When connecting to an IOC running EPICS 3.15 or later, the field name (or the A JSON field modifier may include HTH! |
@anjohnson Thanks! That helps me. We're only talking here about CA (not PVA). From the first link, notice that a "record instance" does not include the |
@anjohnson - I notice there is no advice about "field names". (Perhaps that advice is here?) I assume that such names do not have |
Field names are set by the record type. I wrote
The standard rules for C identifiers can be found here, but apparently I should have said C-89 instead of C-99 because even that version allowed unicode characters to be used in identifiers (who knew?). On that page you have to set the "Standard revision" pull-down at the top to C-89 to see our definition as we haven't tried using unicode characters in field names, and even if the Perl code processes them correctly the result will almost certainly not be portable to all our target compilers. |
Note that I'm reserving the use of subsequent |
Regardless of whether or not these sorts of PV names are correct or legal in any sort of concrete sense, these errors should be customizable at an application level without monkeypatching. That is: I should be able to remove this restriction, and I should also be able to make it more stringent to enforce local PV name standards via writing a function and registering it similar to how we've done this for instantiation callbacks. Right now, you could manually override the
|
Thanks for picking up the discussion around this @prjemian. @anjohnson is correct that this isn't a motor record but a field of a table record (specifically the y translation drive field), which is implemented as a pseudomotor. It has turned out that I can safely redefine my Ophyd device as an EpicsSignalRO in this case, because that position is only being read from for now in my code. However I did try the monkeypatching approach, which works and will be useful if I decide to redefine the device as an EpicsMotor; Thanks @ZLLentz for a practical workaround. |
I'm getting the BadPVName exception
BadPVName: SR05ID01MIR01:t.Y.RBV
raised when attempting a get() on an EpicsMotor.
Although most comments from colleagues suggest that this seems to be a poorly named PV, is it actually illegal in some way?
The original implementation comment suggests it's more of a guideline than a rule 1e973e1
Our legacy code based on caget, which we still need to use, is quite happy to read it and I can't find any rule in the EPICS docs about dots in PV names being disallowed.
I think the current behaviour should be able to be bypassed if necessary if it is enforcing a convention rather than a rule.
We will try to create an alias of the PV for this case.